Super Capacitor DG Cranking Module
In telecom power infrastructure, reliable diesel generator (DG) starting is critical to maintain site uptime during mains failure, yet conventional battery-based cranking systems often suffer from sulfation, temperature sensitivity, frequent maintenance, and reduced lifecycle performance, leading to DG start failures and network outages. The Super Capacitor DG Cranking Module (SCM-120F) by Intelux addresses these challenges with a high-performance super capacitor–based energy storage solution engineered for instant high-current discharge and rapid recharge capability.
Designed specifically for telecom DG starting applications, this module replaces traditional cranking batteries with a maintenance-free, long-life, and temperature-resilient system that delivers consistent starting torque even after prolonged idle periods. Its ultra-fast charge–discharge performance, high cycle life, and robust operation under harsh environmental conditions ensure dependable DG start-up for BTS sites, telecom shelters, and remote network locations. This makes the SCM-120F an ideal solution for telecom power continuity, reduced maintenance visits, and improved DG reliability across distributed telecom infrastructure.
Construction Details:
- Rugged powder-coated metal enclosure designed for industrial environments
- Compact modular construction suitable for panel or DG mounting
- High-capacitance super capacitor cells arranged in series/parallel configuration
- Integrated DC–DC charger module for controlled charging
- Heavy-duty internal bus bars and secure terminal connections
- High insulation and isolation for operational safety
- Designed for continuous operation with minimal maintenance
- Protection against reverse polarity and short-circuit conditions
Benefits:
- High energy density using super capacitor technology
- Rapid charge and discharge capability
- Extremely long operational life compared to conventional batteries
- Maintenance-free operation
- High reliability under frequent cycling conditions
- Safe operation with built-in electrical protections
- Environment friendly (no chemical degradation or acid content)
- Suitable for repeated DG cranking operations
| Parameter | Specification | Specification | Specification | Specification |
| Rated Capacitance | 120 Farad | 190 Farad | 300 Farad | 240 Farad |
| Nominal Voltage | 15.5 V DC | 15.5 V DC | 14.5 V DC | 15.5 V DC |
| Charging Current | 11.5A | 19 A | 19 A | 19 A |
| Input Voltage Range | 40 – 60 V DC | |||
| Charging Method | Constant current charging | |||
| Recharge Time (0–100%) | Approx. 4 minutes | |||
| Recharge Time (from 11 V) | Approx. 40 seconds | |||
| Operating Temperature | 0°C to +55°C | |||
| Expected Life Cycle | > 50,000 cycles | |||
| Discharge Capability | High current discharge suitable for DG cranking | |||
| Enclosure Material | Powder-coated metal enclosure | |||
| Ingress Protection | IP20 | |||
| Mounting Type | Panel / Rack Mount | |||
| Protection Features | Reverse polarity, short-circuit, over-voltage | |||
Applications:
- Diesel Generator (DG) starting systems
- Telecom power backup solutions
- Hybrid power systems
- Industrial power backup applications
- Renewable energy storage interface