DG Cranking 14.5V @ 120F / 190F / 240F / 300F

Super Capacitor DG Cranking Module

In telecom power infrastructure, reliable diesel generator (DG) starting is critical to maintain site uptime during mains failure, yet conventional battery-based cranking systems often suffer from sulfation, temperature sensitivity, frequent maintenance, and reduced lifecycle performance, leading to DG start failures and network outages. The Super Capacitor DG Cranking Module (SCM-120F) by Intelux addresses these challenges with a high-performance super capacitor–based energy storage solution engineered for instant high-current discharge and rapid recharge capability.

Designed specifically for telecom DG starting applications, this module replaces traditional cranking batteries with a maintenance-free, long-life, and temperature-resilient system that delivers consistent starting torque even after prolonged idle periods. Its ultra-fast charge–discharge performance, high cycle life, and robust operation under harsh environmental conditions ensure dependable DG start-up for BTS sites, telecom shelters, and remote network locations. This makes the SCM-120F an ideal solution for telecom power continuity, reduced maintenance visits, and improved DG reliability across distributed telecom infrastructure.

Construction Details:
  • Rugged powder-coated metal enclosure designed for industrial environments
  • Compact modular construction suitable for panel or DG mounting
  • High-capacitance super capacitor cells arranged in series/parallel configuration
  • Integrated DC–DC charger module for controlled charging
  • Heavy-duty internal bus bars and secure terminal connections
  • High insulation and isolation for operational safety
  • Designed for continuous operation with minimal maintenance
  • Protection against reverse polarity and short-circuit conditions
Benefits:
  • High energy density using super capacitor technology
  • Rapid charge and discharge capability
  • Extremely long operational life compared to conventional batteries
  • Maintenance-free operation
  • High reliability under frequent cycling conditions
  • Safe operation with built-in electrical protections
  • Environment friendly (no chemical degradation or acid content)
  • Suitable for repeated DG cranking operations
slide1
ParameterSpecificationSpecificationSpecificationSpecification
Rated Capacitance120 Farad190 Farad300 Farad240 Farad
Nominal Voltage15.5 V DC15.5 V DC14.5 V DC15.5 V DC
Charging Current11.5A19 A19 A19 A
Input Voltage Range40 – 60 V DC
Charging MethodConstant current charging
Recharge Time (0–100%)Approx. 4 minutes
Recharge Time (from 11 V)Approx. 40 seconds
Operating Temperature0°C to +55°C
Expected Life Cycle> 50,000 cycles
Discharge CapabilityHigh current discharge suitable for DG cranking
Enclosure MaterialPowder-coated metal enclosure
Ingress ProtectionIP20
Mounting TypePanel / Rack Mount
Protection FeaturesReverse polarity, short-circuit, over-voltage
Applications:
  • Diesel Generator (DG) starting systems
  • Telecom power backup solutions
  • Hybrid power systems
  • Industrial power backup applications
  • Renewable energy storage interface
  • Critical equipment requiring rapid discharge capability